transformer efficiency

I. Kirish

 

Ekologik muammolar va barqaror energiya echimlari zarurligi, elektr jihozlarining samaradorligi fokal nuqtasiga aylandi. Elektr energiyasini taqsimlash tizimida hal qiluvchi komponentlar bo'lgan transformatorlar energiya samaradorligini aniqlashda muhim rol o'ynaydi. AQSh Energetika vazirligi (DOE) energiya tejashni va energiya sarfini kamaytirish, energiya sarfini kamaytirish va quyi gaz chiqindilarini kamaytirish uchun samaradorlik vositalarini amalga oshirdi. Ushbu maqola transformater energiya samaradorligini samaradorligining asosiy jihatlarini, ularning kelib chiqishi, imtiyozlari, ishlab chiqarish xarajatlari va samaradorligi, ishlab chiqarish xarajatlari va samaradorligi bo'yicha o'zgarganliklari va standartlardagi o'zgarishlar bilan bog'liq muammolar 2010 - 2016.}

 

Ⅱ. Transformator energiya samaradorligi nima?

Transformator energiya samaradorligi foydali quvvat manbaiga kiritilgan quvvatga nisbati nazarda tutadi. Transformator ideal stsenariyda barcha qo'shimcha elektr energiyasini ishlab chiqarish energiyasini hech qanday yo'qotishsiz chiqarish uchun aylantiradi. Biroq, aslida, transformatorlar ikkita asosiy yo'qotishlarni boshdan kechiradilar: yadro yo'qotishlari ({{{{{{{{{{{{{- {{{- {{{- {{{- {- {{{{{{{{{{{- {mis yo'qotishlar deb nomlanadi). Tarkibi transformator yadrosining magnitlanishi va-magetizatsiya qilinishi tufayli olib tashlanadi va transformatorga ulangan yukdan qat'iy nazar doimiydir. Boshqa tomondan, yo'qotishlar oqim orqali oqimning maydoniga mutanosib bo'lib, transformatorning yuklanishi ko'payadi.

Transformator (ē) samaradorligi formuladan foydalangan holda hisoblanadi:

ē=(Chiqish quvvat / kirish quvvat) x 100%.

Yuqori - samaradorlik transformatorlari past yo'qotishlarga ega, demak ular energiya energiyasining katta qismini foydali mahsulotga aylantirishlarini anglatadi. Masalan, 98% samaradorligi bo'lgan transformator kirish energiyasining atigi 2% ni, issiqlik kabi, kam samarali transformator 5% yoki undan ko'pni tarqalishi mumkin.

transformer-efficiency

. Transformator energiya samaradorligiga ta'sir etuvchi asosiy omillar

 

transformer Core Material

1. Materiallar va dizayn:

Asosiy material (masalan, yuqori {{{{- tfic Toyilli, amorf qotishmasi) Güser yo'qolishi, kam - yo'qotish materiallari energiyani buzishni kamaytiradi. Asosiy tuzilma (laminatsiya usuli, xoch -} Concale viloyati) magnit flux zichligiga ta'sir qiladi va optimallashtirilgan dizayni yo'q

Winding Material

2. Moddiy va texnologiyalarni o'tkazish

Yo'l harakati o'tkazgichlarini (mis yoki alyuminiy) o'tkazuvchanligi yukning yo'qotilishini to'g'ridan-to'g'ri ta'sir qiladi, mis missi esa mis. Oyoq burilishlari, xoch - Secal maydoni va kelishuv texnologiyalari bardoshli yo'qotishlarni kamaytirishga ta'sir qiladi.

Transformer Load Factor

3.TRMranmer yuklash faktori

Ishlayotgan yuk va ishlab chiqarish quvvatlari o'rtasidagi mos darajasi samaradorlikka ta'sir qiladi. Uzoq muddatli haddan tashqari yuk ko'tarilishni kuchaytiradi, past yuklash omili - yuk yo'qotish ulushini ko'taradi. Odatda optimal samaradorligi odatda narxlangan yukning 40% -60% miqdorida uchraydi.

 Cooling Method

4. Sovutish usuli

Sovutish samaradorligi moyli va quruq - tsirar transformatorlar orasida o'zgarib turadi. Yuqori {{3} - samaradorlikni sovutish tizimlari (masalan, majburiy havo sovutish, yog 'aylanishini) izolyatsiya va yadro haroratini kamaytiradi.

Manufacturing Process

5. Ishlab chiqarish jarayoni va zararni boshqarish

Asosiy qo'shma davolash, o'rash qalinligi va montajning aniqligi kabi jarayon omillari oqishga va ehtiyotsizlikning buzilishi. Oldindan ishlab chiqarish qo'shimcha yo'qotishlarni kamaytiradi va energiya samaradorligini baholashni kuchaytiradi.

 

Ⅳ. Ichki samaradorlik standartlari nima?

DOE Efficiency Standards

Doe Samarali aloqa standartlari - bu AQShda sotiladigan transformatorlarning turli turlari uchun minimal darajada maqbul energiya samaradorligini aniqlaydigan qoidalar to'plamidir. Ushbu standartlar bozorda transformatorlar energiya ko'rsatkichlariga mos kelishini ta'minlash uchun ishlab chiqilgan, shu bilan elektr tarmoqlarining umumiy energiya sarfini kamaytirish.

Standartlar transformatorlarning keng doirasi, shu jumladan - fazasi va uch - - - faza taqsimlash transformatyorlari, shuningdek muayyan kuch transformatorlari. Transformatorning kuchlanish sinfiga, sig'imi va turdagi yoki quruq {{{4} {- turiga qarab, yadroli yo'qotishlar va yuk tashishlari uchun maksimal qiymatlarni belgilaydi). Masalan, uch - fazasi 10 - {}}} V.10 - {}}} {}}10 - {}} {}}10 -10 -10 -10 -10 -} fazasi ma'lum quvvatni taqsimlashning asosiy chegarasi va DOE standartlariga muvofiq yo'qotishlar uchun maksimal darajada cheklanadi. Ushbu standartlarga rioya qilish AQSh bozoridagi transformatorlarni sotmoqchi bo'lgan ishlab chiqaruvchilarga majburiydir.

 

. Doe Samaradorlik standartlarining kelib chiqishi

Transformatorlar uchun samaradorlik standartlarini ishlab chiqish, energiya tejash va atrof muhitga elektr jihozlarining ta'sirini kuchayish bilan xabardor bo'lishi mumkin. 1970 yillarning energiya inqirozi muhim katalizator edi, Amerika Qo'shma Shtatlarining energiya taqchilligi va energiyadan unumli foydalanish zarurligini ta'kidladi. Vaqt o'tishi bilan, iqlim o'zgarishi munosabati bilan energiya ishlab chiqarish va iste'mol bilan bog'liq issiqxona gazlari chiqindilarini kamaytirishga urg'u kuchaygan.

Amerika Qo'shma Shtatlarida energiya siyosati va tadqiqotlari uchun mas'ul bo'lgan Federal Agentlik federal agentligi, shu jumladan turli xil elektr mahsulotlari, shu jumladan transformatorlar uchun samaradorlik standartlarini rivojlantirish bo'yicha tashabbusni amalga oshirdi. Ushbu standartlar sanoat mutaxassislari, energetika tadqiqotchilari va ekologik guruhlardan kelib chiqqan har tomonlama jarayoni bilan shakllantirildi. Maqsad energiya samaradorligini oshirish va iqtisodiyotning samarali va narxining ishonchli va narxining doimiy mavjudligini ta'minlash o'rtasidagi muvozanatni buzish edi. Standartlar transformator dizayni va ishlab chiqarishning texnologik yutuqlari bilan shug'ullanish, shuningdek energiya tejashni yanada kuchaytirish uchun vaqti-vaqti bilan yangilandi.

 

Transformatorlarning samaradorligi standartlari

Past - voltaj Quruq - turdagi tarqatish transformatorlari.

Yagona - fazasi

Uch - fazasi

kova

2007

Unumdorlik

(%)

2016

Unumdorlik

(%)

O'zgaruvchanlik

%

kova

2007

Unumdorlik

(%)

2016

Unumdorlik

(%)

O'zgaruvchanlik

%

15

97.7

97.70

0.00%

15

97.0

97.89

0.92%

25

98.0

98.00

0.00%

30

97.5

98.23

0.75%

37.5

98.2

98.20

0.00%

45

97.7

98.40

0.72%

50

98.3

98.30

0.00%

75

98.0

98.60

0.61%

75

98.5

98.50

0.00%

112.5

98.2

98.74

0.55%

100

98.6

98.60

0.00%

150

98.3

98.83

0.54%

167

98.7

98.70

0.00%

225

98.5

98.94

0.45%

250

98.8

98.80

0.00%

300

98.6

99.02

0.43%

333

98.9

98.90

0.00%

500

98.7

99.14

0.45%

       

750

98.8

99.23

0.44%

       

1000

98.9

99.28

0.38%

 

Suyuq - Tasalli tarqatilgan transformatorlar

Yagona - fazasi

Uch - fazasi

kova

2010

Unumdorlik

(%)

2016

Unumdorlik

(%)

O'zgaruvchanlik

%

kova

2010

Unumdorlik

(%)

2016

Unumdorlik

(%)

O'zgaruvchanlik

%

10

98.62

98.7

0.08%

15

98.36

98.65

0.29%

15

98.76

98.82

0.06%

30

98.62

98.83

0.21%

25

98.91

98.95

0.04%

45

98.76

98.92

0.16%

37.5

99.01

99.05

0.04%

75

98.91

99.03

0.12%

50

99.08

99.11

0.03%

112.5

99.01

99.11

0.10%

75

99.17

99.19

0.02%

150

99.08

99.16

0.08%

100

99.23

99.25

0.02%

225

99.17

99.23

0.06%

167

99.25

99.33

0.08%

300

99.23

99.27

0.04%

250

99.32

99.39

0.07%

500

99.25

99.35

0.10%

333

99.36

99.43

0.07%

750

99.32

99.40

0.08%

500

99.42

99.49

0.07%

1000

99.36

99.43

0.07%

667

99.46

99.52

0.06%

1500

99.42

99.48

0.06%

833

99.49

99.55

0.06%

2000

99.46

99.51

0.05%

       

2500

99.49

99.53

0.04%

 

O'rta - Voltage Quruq - turdagi tarqatish transformatorlari

2010 yil samaradorligi (%)

Yagona - fazasi

Uch - fazasi

kova

Bil

kova

Bil

20-45kv

46-95kv

96 kv dan katta yoki teng

20-45kv

46-95kv

96 kv dan katta yoki teng

Samaradorlik (%)

Samaradorlik (%)

Unumdorlik

(%)

Samaradorlik (%)

Samaradorlik (%)

Samaradorlik (%)

15

98.1

97.86

 

15

97.50

97.18

 

25

98.33

98.12

 

30

97.90

97.63

 

37.5

98.49

98.3

 

45

98.10

97.86

 

50

98.6

98.42

 

75

98.33

98.12

 

75

98.73

98.57

98.53

112.5

98.49

98.30

 

100

98.82

98.67

98.63

150

98.60

98.42

 

167

98.96

98.83

98.80

225

98.73

98.57

98.53

250

99.07

98.95

98.91

300

98.82

98.67

98.63

333

99.14

99.03

98.99

500

98.86

98.83

98.80

500

99.22

99.12

99.09

750

99.07

98.95

98.91

667

99.27

99.18

99.15

1000

99.14

99.03

98.99

833

99.31

99.23

99.20

1500

99.22

99.12

99.09

       

2000

99.27

99.18

99.15

       

2500

99.31

99.23

99.20

 

2016 moliyaviy samaradorlik (%)

Yagona - fazasi

Uch - fazasi

kova

Bil

kova

Bil

20-45kv

46-95kv

96 kv dan katta yoki teng

20-45kv

46-95kv

96 kv dan katta yoki teng

Samaradorlik (%)

Samaradorlik (%)

Unumdorlik

(%)

Samaradorlik (%)

Samaradorlik (%)

Samaradorlik (%)

15

98.10

97.86

 

15

97.50

97.18

 

25

98.33

98.12

 

30

97.90

97.63

 

37.5

98.49

98.30

 

45

98.10

97.86

 

50

98.60

98.42

 

75

98.33

98.13

 

75

98.73

98.57

98.53

112.5

98.52

98.36

 

100

98.82

98.67

98.63

150

98.65

98.51

 

167

98.96

98.83

98.80

225

98.82

98.69

98.57

250

99.07

98.95

98.91

300

98.93

98.81

98.69

333

99.14

99.03

98.99

500

99.09

98.99

98.89

500

99.22

99.12

99.09

750

99.21

99.12

99.02

667

99.27

99.18

99.15

1000

99.28

99.20

99.11

833

99.31

99.23

99.20

1500

99.37

99.30

99.21

       

2000

99.43

99.36

99.28

       

2500

99.47

99.41

99.33

 

VII. Transformatorlar Doe standartlaridan ozod qilingan

7

Doe Samaradorlik standartlari ko'plab tarqatish vositalariga, ixtisoslashtirilgan funktsiyalar yoki {{1} stsenariylar uchun mo'ljallangan ba'zi birlashtirilgan transforders {{} stsenariylari uchun mo'ljallangan. Quyida funktsional stsenariylar tomonidan tashkil etilgan Doe Samaradorligi talablariga bino bo'lmagan transformatorlarning toifali taqsimlanishi keltirilgan:

1. Maxsus ulanish va himoyachi vositalari

  • Avtotransformer: Ellik kuchlanish konversiyasi uchun bitta shamol ishlatadi; Strukturaviy dizayn standart samaradorlik qoidalarini qo'llash mumkin emas.
  • Yerga tutashtiruvchi: Umumiy energiya samaradorligi bo'yicha xavfsizlikni ta'minlash, tizimni magistral himoya qilish uchun qurilgan.
  • Tartibga soluvchi transformator: Tez-tez kuchlanishni to'g'rilashni talab qiladi (kattaroq yoki 20% ga teng); Energiya tejash emas, kuchlanishni tartibga solish uchun mo'ljallangan.

2. Sanoat - Muayyan transformatorlar

  • Mashina - Transformator (boshqarish) Transformator: Tekshiruv uchun moslashtirilgan - vositalar nazorati, energiya samaradorligi bo'yicha uskunalar mosligini ustuvorlashtirish.
  • Payvandlash transformatori: Tailored for welding processes (needing instant high - current output); Dizayn mantiq standart samaradorlik maqsadlaridan farq qiladi.
  • Haydash (izolyatsiya) transformator: - chastotali drayver tizimlari, - umumiy samaradorlik qoidalaridan ozod qilingan - chastotali drayveri tizimlariga xizmat qiladi.

3. Maxsus - tuzilmalar va maqsadli transformatorlar

  • {{0} veniled transformator: Muhrlangan / passiv sovishi bilan bog'liq; Dizayn standart samarador emas, balki kosmik moslashishni ustuvor ahamiyat beradi.
  • Muhrlangan transformator: Keng - yopiq tuzilmasi issiqlik boshqaruvi va samaradorlikni optimallashtirishni cheklaydi - ozod qiladi.
  • Maxsus - XALQ TRANSIYASI: Maslahat uchun qurilgan - mos keladigan stsenariylar (masalan, sinov uskunalari); Funktsiya energiya samaradorligidan ustundir.

4. Quvvat - Contsion - Muayyan transformatorlar

  • Rektrier transformatori: AC - CRC - DC konversiyasiga - DC konversiyasi - tishli vositalarga moslikni ({2}} standart samaradorligini oshirishni talab qiladi.
  • Uzluksiz elektr ta'minoti (UPS) transformatorShoshilinch energiya ishonchliligini ta'minlaydi; majburiy samaradorlik ustidan chidamlilikni afzal qiladi.
  • Sinov transformatori: Test sinovlari uchun ishlatiladi (moslashuvchan kuchlanish / joriy sozlash); Energiya tejash emas, sinov funktsiyalari uchun mo'ljallangan.

 

VIII. Ishlab chiqarish qiymati va samaradorligi o'rtasidagi bog'liqlik

unit-cost

VIII. Ishlab chiqarish qiymati va samaradorligi o'rtasidagi bog'liqlik

Transformatorlarning ishlab chiqarish xarajatlari va ularning energiya samaradorligi bo'yicha kompleks aloqalar mavjud. Umuman olganda, yuqori - samaradorlik transformatorlari ishlab chiqarish xarajatlarini ko'paytirishi mumkin bo'lgan ilg'or materiallar va ishlab chiqarish texnikasini talab qiladi. Masalan, asosiy yo'qotishlarni kamaytirish uchun ishlab chiqaruvchilar yuqori -} sifatli magnit materiallardan, masalan, - Silikon po'latdan yasalgan magnit materiallardan foydalanishlari mumkin. Ushbu materiallar ko'pincha - Samarali transformatorlarda ishlatiladigan standart materiallardan qimmatroqdir.

Bundan tashqari, yuqori - samaradorlik transformatorlari uchun ishlab chiqarish jarayoni ancha aniq va vaqt sarflashi mumkin. Qurilishni to'g'irlash va iliq izolyatsiya materiallarini kesish uchun tazelik tiniqliklar ko'pincha yuk yo'qotishlarini minimallashtirish uchun talab qilinadi. Ushbu omillar yuqori ishlab chiqarish xarajatlariga yordam beradi. Biroq, uzoq vaqt - Tuzatuvlar istiqbolidan, ushbu transformatorlarning samaradorligi - foydalanuvchilar uchun energiya tejashga olib kelishi mumkin. Transformatorning umri davomida 20 - 30 yil yoki undan ko'p bo'lishi mumkin bo'lgan umrbod energiya sarfi boshlang'ich xarid narxini qoplashi mumkin.

Ishlab chiqaruvchilar ishlab chiqarish xarajatlari va samaradorligi o'rtasidagi to'g'ri muvozanatni topish qiyinchiliklariga duch kelishadi. Ular bozorda raqobatdosh qolganda, ular samaradorlik standartlariga javob beradigan transformatorlarni ishlab chiqarishlari kerak. Bu - narxini topish va ishlab chiqarish samaradorligini oshirish uchun doimiy tadqiqotlar va rivojlanishni innovatsion dizaynerlik yoki yangi, ortiq arzon materiallardan foydalanish, bu hali ham yaxshi energiya tejash xususiyatlarini taqdim etish.

 

IX. 2010 - 2016 standart o'zgarishlar bilan bog'liq muammolar

2010 - 2016 Transformatsiyalarning samaradorligi standartlarida jiddiy o'zgarishlar yuz berdi. Ushbu o'zgarishlar energiya sarfini yanada kamaytirish va barqaror energiyadan foydalanishni rivojlantirishga qaratilgan. Biroq, ular ishlab chiqaruvchilar va umuman sanoat uchun bir nechta muammolarni keltirib chiqardilar.

Ishlab chiqaruvchilarning yangi, yanada qat'iy standartlarni qondirish uchun ishlab chiqaruvchilarni va mahsulot dizaynlarini tezda tezda moslashtirish uchun asosiy muammolardan biri bo'ldi. Bu, pasayish chegaralarini qondiradigan yangi transformator dizaynlarini rivojlantirish bo'yicha tadqiqotlar va rivojlanishga muhim sarmoya kiritish kerak. Mavjud ishlab chiqarish liniyalari ko'pincha o'zgartirilishi yoki re - Muhandisli bo'lib, ular qisqa - qisqa muddatli xarajatlarni ko'paytirishga olib keldi.

Ta'mirlash zanjiri menejmenti nuqtai nazaridan ham qiyin kechdi. Ishlab chiqaruvchilar samaradorlikni yaxshilash uchun turli xil materiallardan foydalanishga kirishdilar, ular ushbu yangi materiallarning barqaror ta'minlanishini ta'minlashi kerak edi. Masalan, agar ishlab chiqaruvchi magnit yadro materialining yangi turidan foydalana boshlasa, ular pulni ishonchli etkazib beruvchilarni topishlari va uzoq muddatli muzokaralar olib borishi kerak edi. Nuqta tarmog'ida uzilishlar ishlab chiqarish kechikishiga va xarajatlarni ko'paytirishga olib kelishi mumkin.

Yana bir muammo - yangi transformatorlarning samaradorligi bilan bog'liq edi. Uzoq - Muddatli energiya tejash aniq edi, bu samarali transformatorlarning boshlang'ich xarajatlari, ayniqsa sotib olishni oqlash uchun ba'zi mijozlar uchun, ayniqsa imtiyozli bo'lganlar uchun qiyinlashtirdi. Bu o'z-ekologik va energiyani tejashga qaramay, bozorda yangi, yanada samarali transformatorlarni qabul qilishning potentsial pasayishiga olib keldi.

transformer DOE

 

X. xulosasi

Transformator Doe Samaradorlik standartlari Amerika Qo'shma Shtatlarining energiya tejashni va atrof-muhitga ta'sirini kamaytirish bo'yicha sa'y-harakatlarining ajralmas qismidir. Transformator energiya samaradorligini, DOE standartlari, ularning kelib chiqishi, shartlari, xarajatlar va samaradorlik o'rtasidagi munosabatlar va standart o'zgarishlarning o'zaro bog'liqligi, barcha manfaatdor tomonlarning elektr sanoatidagi barcha manfaatdor tomonlar uchun hal qiluvchi ahamiyatga ega. Texnologiya rivojlanib borayotgani sayin, Die ushbu standartlarni yanada yangilashi va kuchaytirishi kutilmoqda. Ishlab chiqaruvchilar ushbu standartlarga javob berishni davom ettirishlari kerak, shuningdek xarajatlar va korxonalar o'zlarining pastki chizig'i va atrof-muhit uchun samarali transformatorlarga sarmoya kiritishning uzoq muddatli kredit qiymatiga ega bo'lishlari kerak.